PROCESS ID: 1000ANG DESCRIPTION: 1000 ANG OX AT 900 DEG C GS 3/29/89 BANK: 1 TUBES: 1,2,3,4,7 REUSE: YES 0001.0000 IDLE 0001.0005 STEP N2=2.5 0001.0010 STEP O2HI=OFF 0001.0015 STEP O2HI=0 0001.0020 STEP TEMPL=800 0001.0025 STEP TEMPC=800 0001.0030 STEP TEMPS=800 0001.0035 STEP UNLOAD=OFF 0001.0040 STEP LOAD=ON 0001.0045 STEP SPEED=10 0001.0050 STEP TCU LEARN=OFF 0005.0000 BOAT PULL 0005.0005 STEP TIME:00:00:00 0005.0010 STEP N2=5.0 0005.0015 STEP TEMPL=700 0005.0020 STEP TEMPC=750 0005.0025 STEP TEMPS=800 0005.0030 STEP LOAD=OFF 0005.0035 STEP UNLOAD=ON 0005.0040 STEP SPEED=10 0005.0045 STEP TCU LEARN=OFF 0005.0050 STEP IF ALMACK=ON GOTO 0010 0010.0000 BOAT IN 0010.0005 STEP TIME:00:20:00 0010.0010 STEP TEMPL=800 0010.0015 STEP TEMPC=800 0010.0020 STEP TEMPS=800 0010.0025 STEP UNLOAD=OFF 0010.0030 STEP LOAD=ON 0010.0035 STEP SPEED=10 0010.0040 STEP TCU CTLID=1 0010.0045 STEP TCU LEARN=OFF 0015.0000 RAMP UP TO 900 DEG +- 1.0 0015.0005 STEP TIME:00:20:00 0015.0010 STEP TEMPL=900 0015.0015 STEP TEMPC=900 0015.0020 STEP TEMPS=900 0015.0025 STEP N2=2.4 0015.0030 STEP O2LO=100 0015.0035 STEP TCU CTLID=3 0015.0040 STEP TCU LEARN=OFF 0020.0000 DRY OX 0020.0005 STEP TIME:00:10:00 0020.0010 STEP N2=OFF 0020.0015 STEP N2=0 0020.0020 STEP O2LO=OFF 0020.0025 STEP O2LO=0 0020.0030 STEP O2HI=2500 0020.0035 STEP TCU CTLID=3 0020.0040 STEP TCU LEARN=OFF 0025.0000 STEAM 0025.0005 STEP TIME:00:41:00 0025.0010 STEP H2/O2=150 0025.0015 STEP O2HI=1000 0025.0020 STEP TCU CTLID=22 0025.0025 STEP TCU LEARN=OFF 0030.0000 DRY OX 0030.0005 STEP TIME:00:10:00 0030.0010 STEP H2/O2=OFF 0030.0015 STEP H2/O2=0 0030.0020 STEP O2HI=2500 0030.0025 STEP TCU CTLID=3 0030.0030 STEP TCU LEARN=OFF 0035.0000 RAMP DOWN 0035.0005 STEP TIME:00:20:00 0035.0010 STEP O2HI=OFF 0035.0015 STEP O2HI=0 0035.0020 STEP N2=5.0 0035.0025 STEP TEMPL=750 0035.0030 STEP TEMPC=750 0035.0035 STEP TEMPS=750 0035.0040 STEP TCU LEARN=OFF 0040.0000 BOAT OUT 0040.0005 STEP TIME:00:00:00 0040.0010 STEP TEMPL=700 0040.0015 STEP TEMPC=750 0040.0020 STEP TEMPS=775 0040.0025 STEP TCU LEARN=OFF 0040.0030 STEP LOAD=OFF 0040.0035 STEP UNLOAD=ON 0040.0040 STEP SPEED=10 0040.0045 STEP IF ALMACK=ON GOTO 0045 0045.0000 END 0045.0005 STEP END PROCESS