Subject: Re: Problem raith SNF 2007-08-22 00:33:24: water flow failure
From: jwc@snf.stanford.edu
Date: Wed, 22 Aug 2007 09:48:10 -0700

increased pressure on chiller to 90 psi which is safe maximum.  Water flow reduced to
0.6 lpm (50% od specification.)
This is likely a recurrent problems until RAITH can resolve this issue with replacement
of E/O card cooling manifolds.